Product Introduction

Product Descriptions


Water leak detection controller

(LK08-C1-1CH-B / N)

LK08-C1-1CH-B
LK08-C1-1CH-B
LK08-C1-1CH-N
LK08-C1-1CH-N

- Product Information

  • 1-channel water leak detection controller
  • Detection of conductive liquids (water, chemical solutions)
  • Dry contact individual contact output
  • Compact size, compact functionality product
  • When using the disconnection function, a water leak detection stop connector is required (EDS03)
  • Refer to the channel wiring method manual
  • Refer to the manual for diagnosis and response methods when errors occur
Classification
Specifications
Product name
Water leak detection controller
Model name
LK08-C1-1CH-B
LK08-C1-1CH-N 
Dimensions
64mm(W) X 43mm(H) X 27mm(D)
Channel
1 channel
Input voltage
DC24V
Power Consumption
1W
Relay Output

Default N.O X 1CH

NC (possible after firmware change)

Main function
Conductive liquid detection
Sensor disconnection detection
Buzzer sound in case of leak (80dB)

Conductive liquid detection

Buzzer sound in case of leak (80dB)

Certification
KC, CE, UL, S Mark

Water leak detection controller

(LK15-C1-4CH-B)

- Product Information

  • 4- channel water leak detection controller
  • Detection of conductive liquids (water, chemical solutions)
  • Sensor value setting and inspection possible through LCD display
  • History LOG management
  • Dry contact individual contact output
  • RS485 communication output, leakage and disconnection integrated relay output
  • Requires water leak detection termination connector (EDS03)
  • Refer to the channel wiring method manual
  • Refer to the manual for diagnosis and response methods when errors occur
Classification
Specifications
Product name
Water leak detection controller
Model name
LK15-C1-4CH-B
Dimensions
95mm(W) X 131.5mm(H) X 27.4mm(D)
Channel
Up to 4 channels
Input voltage
DC18~36V
Power Consumption
4W
Relay Output

N.O or N.C X 4CH

RS485
(RTU Modbus)
Leak detection, release transmission
Disconnection detection, release transmission
Main function
Conductive liquid detection
Sensor disconnection detection

Log data storage

Buzzer sound in case of leak (80dB)
Certification
KC, CE, UL, S Mark

Water leak detection controller

(LK19-C1-12CH-B) 

- Product Information

  • 12-channel water leak detection controller
  • Detection of conductive liquids (water, chemical solutions)
  • Relay output for each channel through linking LK19-RY1-12CH without the need for a relay terminal block
  • Sensor value setting and inspection possible through LCD display
  • History LOG management
  • Dry contact individual contact output
  • RS485 communication output, leakage and disconnection integrated relay output
  • Requires water leak detection termination connector (EDS03)
  • Refer to the channel wiring method manual
  • Refer to the manual for diagnosis and response methods when errors occur
Classification
Specifications
Product name
Water leak detection controller
Model name
LK19-C1-12CH-B
Dimensions
87.5mm(W) X 136mm(H) X 24.5mm(D) 
Channel
Up to 12 channels
Input voltage
DC24V
Power Consumption
6W
Relay Output

Leak detection X 2CH

Disconnection detection X 2CH

Normal detection X 2CH

Alarm detection X 2CH

RS485
(RTU Modbus)
Leak detection, release transmission
Disconnection detection, release transmission
Main function
Conductive liquid detection
Sensor disconnection detection

Log data storage

Buzzer sound in case of leak (80dB)
Certification
KC, UL

Leakage distance detection controller

(LK14-C1) 

- Product Information

  • 1-channel water leak distance detection controller
  • Detection of conductive liquids (water, chemical solutions)
  • Sensor value setting and inspection possible through LCD display
  • History LOG management
  • Dry contact individual contact output
  • RS485 communication output, leakage and disconnection integrated relay output
  • Leakage distance detection terminal connector required (EDS02)
  • Refer to the channel wiring method manual
  • Refer to the manual for diagnosis and response methods when errors occur
Classification
Specifications
Product name
Leakage distance detection controller
Model name
LK14-C1
Dimensions
95mm(W) X 131.5mm(H) X 27.4mm(D)
Channel
1 channel
Input voltage
DC24V
Power Consumption
4W
Relay Output

(N.O or N.C) X 1CH 

RS485
(RTU Modbus)
Leak detection, release transmission
Disconnection detection, release transmission
Main function
Conductive liquid detection
Sensor disconnection detection

Log data storage

Buzzer sound in case of leak (80dB)
Certification
KC, CE, UL, FCC

Chemical solution detection controller

(LK14-C1-MTPH-1CH / LK14-C1-MTPH-4CH)

LK14-C1-MTPH-1CH
LK14-C1-MTPH-1CH
LK14-C1-MTPH-4CH
LK14-C1-MTPH-4CH

- Product Information

  • 1-channel or 4-channel chemical solution detection controller
  • Capacitance detection of chemical solutions (acids, bases)
  • Sensor value setting and inspection possible through LCD display
  • History LOG management
  • Dry contact individual contact output
  • Requires chemical solution detection termination connector (EDS06)
  • RS485 communication output, leakage and disconnection integrated relay output
  • Refer to the channel wiring method manual
  • Refer to the manual for diagnosis and response methods when errors occur
Classification
Specifications
Product name
Chemical solution detection controller
Model name
LK14-C1-MTPH-1CH
LK14-C1-MTPH-4CH
Dimensions
95mm(W) X 131.5mm(H) X 27.4mm(D)
Channel
1 channel
Up to 4 channels
Input voltage
DC24V
Power Consumption
4W
Relay Output

(N.O or N.C) X 1CH 

(N.O or N.C) X 4CH 
RS485
(RTU Modbus)
Leak detection, release transmission
Disconnection detection, release transmission
Main function
Oil and organic solvent detection
Sensor disconnection detection

Log data storage

Buzzer sound in case of leak (80dB)
Certification
KC, UL, CE

Chemical solution detection controller

(LK19-C1-MTPH-12CH)

- Product Information

  • 12-channel chemical solution detection controller
  • Capacitance detection of chemical solutions (acids, bases)
  • Relay output for each channel through linking LK19-RY1-12CH without the need for a relay terminal block
  • Sensor value setting and inspection possible through LCD display
  • History LOG management
  • Dry contact individual contact output
  • Requires chemical solution detection termination connector (EDS06)
  • RS485 communication output, leakage and disconnection integrated relay output
  • Refer to the channel wiring method manual
  • Refer to the manual for diagnosis and response methods when errors occur
Classification
Specifications
Product name
Chemical solution detection controller
Model name
LK19-C1-MTPH-12CH
Dimensions
87.5mm(W) X 136mm(H) X 24.5mm(D)
Channel
Up to 12 channels
Input voltage
DC24V
Power Consumption
6W
Relay Output

Leak detection X 2CH

Disconnection detection X 2CH

Normal detection X 2CH

Alarm detection X 2CH

RS485
(RTU Modbus)
Leak detection, release transmission
Disconnection detection, release transmission
Main function
Oil and organic solvent detection
Sensor disconnection detection

Log data storage

Buzzer sound in case of leak (80dB)
Certification
KC, UL

Oil and organic solvent solution detection controller

(LK08-C1-HDC01)

- Product Information

  • 1-channel oil and organic solvent solution detection controller
  • Senses conductive resistance of oil/ organic solvents
  • Sensor value setting and inspection possible through LCD display
  • History LOG management
  • Dry contact individual contact output
  • Oil and organic solvent solution detection termination connector required (EDS04)
  • RS485 communication output, leakage and disconnection integrated relay output
  • Refer to the channel wiring method manual
  • Refer to the manual for diagnosis and response methods when errors occur
Classification
Specifications
Product name
Oil and organic solvent solution detection controller
Model name
LK08-C1-HDC01
Dimensions
95mm(W) X 131.5mm(H) X 27.4mm(D)
Channel
1 channel
Input voltage
DC24V
Power Consumption
4W
Relay Output

(N.O or N.C) X 1CH 

RS485
(RTU Modbus)
Leak detection, release transmission
Disconnection detection, release transmission
Main function
Oil and organic solvent detection
Sensor disconnection detection

Log data storage

Buzzer sound in case of leak (80dB)
Certification
KC, UL, CE

Oil and organic solvent solution detection controller

(LK14-C1-MT-4CH)

- Product Information

  • 4-channel oil and organic solvent solution detection controller
  • Senses conductive resistance of oil/ organic solvents
  • Sensor value setting and inspection possible through LCD display
  • History LOG management
  • Dry contact individual contact output
  • Oil and organic solvent solution detection termination connector required (EDS04)
  • RS485 communication output, leakage and disconnection integrated relay output
  • Refer to the channel wiring method manual
  • Refer to the manual for diagnosis and response methods when errors occur
Classification
Specifications
Product name
Oil and organic solvent solution detection controller
Model name
LK14-C1-MT-4CH
Dimensions
95mm(W) X 131.5mm(H) X 27.4mm(D)
Channel
Up to 4 channels
Input voltage
DC24V
Power Consumption
4W
Relay Output

(N.O or N.C) X 4CH 

RS485
(RTU Modbus)
Leak detection, release transmission
Disconnection detection, release transmission
Main function
Oil and organic solvent detection
Sensor disconnection detection

Log data storage

Buzzer sound in case of leak (80dB)
Certification
KC, UL, CE

Oil and organic solvent solution detection controller

(LK19-C1-MT-12CH)

- Product Information

  • 12-channel oil and organic solvent solution detection controller
  • Senses conductive resistance of oil/ organic solvents
  • Relay output for each channel through linking LK19-RY1-12CH without the need for a relay terminal block
  • Sensor value setting and inspection possible through LCD display
  • History LOG management
  • Dry contact individual contact output
  • Oil and organic solvent solution detection termination connector required (EDS04)
  • RS485 communication output, leakage and disconnection integrated relay output
  • Refer to the channel wiring method manual
  • Refer to the manual for diagnosis and response methods when errors occur
Classification
Specifications
Product name
Oil and organic solvent solution detection controller
Model name
LK19-C1-MT-12CH
Dimensions
87.5mm(W) X 136mm(H) X 24.5mm(D)
Channel
Up to 12 channels
Input voltage
DC24V
Power Consumption
6W
Relay Output

Leak detection X 2CH

Disconnection detection X 2CH

Normal detection X 2CH

Alarm detection X 2CH

RS485
(RTU Modbus)
Leak detection, release transmission
Disconnection detection, release transmission
Main function
Oil and organic solvent detection
Sensor disconnection detection

Log data storage

Buzzer sound in case of leak (80dB)
Certification
KC, UL

Multi-leak master controller

(LK18-C2-4CH)

- Product Information

  • 4-channel multi-leak and fire detection master controller
  • Chemical solution and oil / organic solvent complex leak detection
  • Detection target solution : Chemical solution and oil/organic solvent depending on the channel
  • Location can be confirmed by section when leak or fire is detected
  • Up to 15 lower slave module channels can be connected (MAX 60 channels)
  • Sensor value setting and inspection possible through LCD display
  • History LOG management
  • Requires chemical solution detection terminal connector (LK18WC-EDS16)
    Oil/ organic solvent detection termination connector required (LK18WC-EDS13)
  • Acquired new product certification from the Ministry of Trade, Industry and Energy (NEP, 2019)
  • Refer to the channel wiring method manual
  • Refer to the manual for diagnosis and response methods when errors occur
Classification
Specifications
Product name
Multi-leak master controller
Model name
LK18-C2-4CH
Dimensions
101mm(W) X 136mm(H) X 25mm(D)
Channel
Up to 4 channels
Input voltage
DC24V
Power Consumption
10W
Relay Output

Leak detection X 4CH (N.O or N.C)

Disconnection detection X 4CH (N.O or N.C)

Temperature detection (N.O or N.C)

RS485
(RTU Modbus)
Leak detection, release transmission
Disconnection detection, release transmission
Transmit overtemperature alarm
Slave module communication error transmission
Main function
Conductive liquid detection
Sensor disconnection detection

Log data storage

Buzzer sound in case of leak (80dB)
Certification
NEP, KC, UL, CE

Battery leak detection controller

(LK20-DH-4CH)

- Product Information

  • 4-channel battery leak detection controller
  • Battery electrolyte detection
  • Sensor value setting and inspection possible through LCD display
  • History LOG management
  • Dry contact individual point output
  • RS485 communication output, leakage and disconnection integrated relay output
  • Refer to the channel wiring method manual
  • Refer to the manual for diagnosis and response methods when errors occur
Classification
Specifications
Product name
Battery leak detection controller
Model name
LK20-DH-4CH
Dimensions
101mm(W) X 136mm(H) X 25mm(D)
Channel
1 channel
Input voltage
DC24V
Power Consumption
4W
Relay Output

(N.O or N.C) X 4CH 

RS485
(RTU Modbus)
Leak detection, release transmission
Disconnection detection, release transmission
Main function
Conductive liquid detection
Sensor disconnection detection

Log data storage

Buzzer sound in case of leak (80dB)
Certification
KC

Integrated master controller

(LK08-MC200)

- Product Information

  • Check leakage, disconnection, and communication error status through LCD display
  • Leak alarm module maximum 200 connections possible
  • History LOG management
  • Transmit event information to integrated disaster prevention center or to server
  • Refer to the channel wiring method manual
  • Refer to the manual for diagnosis and response methods when errors occur
Classification
Specifications
Product name
Integrated Master Controller
Model name
LK08-MC200
Dimensions
280mm(W) X 260mm (H) X 91mm (D)
Channel
128 channels
Input voltage
AC110~220V
Power Consumption
10W
Relay Output

Relay (N.C, N.O)

Broken Relay (N.C, N.O)

Communication error Relay (N.C, N.O)

RS485
(RTU Modbus)
Leak detection transmission, point of occurrence, cancellation transmission

Disconnection detection, termination transmission

Communication error transmission
Main function
Check lower alarm module communication status
Receive local events

Log data storage

Buzzer sound in case of leak (80dB)
Certification
KC, CE

12-channel controller dedicated relay board

(LK19-RY1-12CH)

- Product Information

  • 12-channel relay dedicated relay board
  • Dry contact individual point output
  • RS485 communication output
  • Refer to the channel wiring method manual
  • Refer to the manual for diagnosis and response methods when errors occur
Classification
Specifications
Product name
12-channel controller dedicated relay board
Model name
LK19-RY1-12CH
Dimensions
87.5mm(W) X 136mm(H) X 33.7mm(D)
Channel
Up to 12 channels
Input voltage
DC24V
Power Consumption
6W
Relay Output

Dry Output(N.O or N.C) X 12

Lamp Output(N.O) X 12

RS485
(RTU Modbus)
9600bps, 8DataBits, 1Stop Bit, None Parity
Main function
Relay output function
RS485 communication function
Certification
KC